Name: 
 

NEC Practice



Multiple Choice
Identify the choice that best completes the statement or answers the question.
 

 1. 

The meaning of approved is ____.
a.
listed by a Nationally Recognized Testing Laboratory (NRTL)
b.
acceptable to the National Electrical Code®
c.
acceptable to the architect or engineer designing the job
d.
acceptable to the authority having jurisdiction
 

 2. 

In the international system of units, the prefix milli- means ____.
a.
one hundredth
b.
one thousandth
c.
one millionth
d.
one billionth
 

 3. 

Nationally Recognized Testing Laboratories (NRTL) ____ electrical products to provide a basis for approval by inspectors in the field.
a.
approve
b.
test and list
c.
rate
d.
none of these
 

 4. 

Branch-circuit conductors at outlet boxes are required to have at least ____ inches of free length for making splices and connections. The length of conductor is measured is from where the conductors enter the box.
a.
4
b.
6
c.
8
d.
12
 

 5. 

NEC® 300.15 requires that a ____ be installed at each conductor splice or connection point.
a.
insulated wire connector
b.
outlet box
c.
grounding electrode conductor
d.
none of these
 

 6. 

Ceiling-suspended (paddle) fans are required to be installed on ____.
a.
metallic boxes only
b.
boxes listed for supporting fixtures weighing fifty pounds or more
c.
boxes marked "acceptable for fan support"
d.
boxes secured directly to a ceiling joist or other structural element
 

 7. 

According to the NEC®, unless “listed” for the purpose, electrical wall boxes shall not be mounted back-to-back in walls because ____.
a.
sound may be transmitted from room to room.
b.
it reduces the fire resistance of the wall.
c.
there is not sufficient room in the wall cavity to mount electrical wall boxes back-to-back.
d.
all of these.
 

 8. 

According to ____, unused knockouts and other openings in electrical boxes and cabinets are required to be closed.
a.
Article 250
b.
NEC® 110.12(A)
c.
NEC® 314.17 (D), Fine Print Note
d.
both b and c
 

 9. 

NEC® 210.52 on receptacles in residences deals with ____.
a.
the "6-foot rule"
b.
GFCI protection of outdoor receptacles
c.
mounting height
d.
ganged receptacles
 

 10. 

In construction of one- and two-family dwellings, the electrical circuits are usually designed by the ____.
a.
electrician
b.
architect
c.
consulting engineer
 

 11. 

A 20-ampere branch circuit requires ____ conductors, ignoring the effects of voltage drop.
a.
14 AWG copper
b.
14 AWG aluminum
c.
12 AWG copper
d.
12 AWG aluminum
 

 12. 

Where fixed glass panels (i.e., windows or non-sliding parts of door) do not permit installation of wall-mounted receptacles, ____ are typically used to satisfy the receptacle spacing requirements of NEC® 210.52(A)(1).
a.
extension cords
b.
floor-mounted receptacles
c.
quad receptacles
d.
outdoor GFCI-protected receptacles
 

 13. 

Is a receptacle required on a 3 ft (900 mm) wall space behind a door that is normally left open?
a.
yes
b.
no
 

 14. 

Small appliance receptacle outlets ____ required to be included in the 3 volt-ampere per square foot load calculation.
a.
are
b.
are not
 

 15. 

Wire sizes up through No. 4/0 are expressed in American Wire Gauge (AWG).  Wire sizes larger than 4/0 AWG are expressed in ____.
a.
metric units
b.
kcmil
c.
diameter
d.
radians
 

 16. 

Section 310.3 requires that conductors 8 AWG and larger must be ____ when installed in a raceway.
a.
grounded
b.
bonded
c.
stranded
d.
none of these
 

 17. 

Multiple receptacles connected to a 20-ampere branch circuit are required to be rated ____.
a.
15 amperes
b.
20 amperes
c.
125 volts
d.
either a or b
 

 18. 

Older electrical books and plans sometimes use the term "MCM," which means the same thing as ____.
a.
metric
b.
kcmil
c.
A.I.C.
d.
GFCI
 

 19. 

Connectors marked ____ are suitable for use with aluminum, copper, or copper-clad conductors.  Connectors not so marked are for use with copper conductors only.
a.
CO-ALR
b.
AL/CU
c.
UL 9
d.
both a and b
 

 20. 

Under certain circumstances, the grounded conductors of a residential service ____ permitted to be sized smaller than the phase conductors.
a.
are
b.
are not
 

 21. 

Closed-loop and programmed power systems for residences are covered in Article ____.
a.
210
b.
240
c.
300
d.
780
 

 22. 

Type NM cable can be run in all the following locations, except for ____.
a.
concealed in dry locations
b.
concealed in damp and moist locations
c.
exterior masonry block or tile walls
d.
both b and c
 

 23. 

When nonmetallic-sheathed cable is used as a fixture whip above an accessible ceiling, it ____.
a.
is not required to be secured
b.
may be up to 6 ft (1.8 m) in length
c.
is required to be plenum-rated
d.
all of these
 

 24. 

Armored cable includes a(n) ____ to insure a low-impedance grounding path.
a.
insulated equipment grounding conductor (green ground)
b.
bare equipment grounding conductor
c.
internal bonding strip
d.
interlocking armor
 

 25. 

Type AC cable is manufactured with ____ phase conductors.
a.
two
b.
three
c.
four
d.
all of these
 

 26. 

Residential wiring must be installed in raceways under which of the following condition(s)?
a.
cement of cinder block construction
b.
poured concrete construction
c.
where required by local electrical codes
d.
all of these
 

 27. 

As covered by Article 352, rigid nonmetallic conduit is permitted to do all of the following, except for ____.
a.
be installed concealed
b.
support lighting fixtures
c.
support conduit bodies
d.
be used in damp and wet locations
 

 28. 

Liquidtight flexible nonmetallic conduit is subject to which of the following limitations?
a.
cannot be used in direct sunlight, unless marked for this application
b.
can become brittle in extremely cold temperatures
c.
cannot be direct-buried, except when marked for this application
d.
all of these
 

 29. 

When using individual conductors smaller than 6 AWG in a raceway, which of the following colors of insulation are not permitted for the grounded conductor (neutral), ____.
a.
green with yellow stripe
b.
white
c.
green with three white stripes
d.
gray
 

 30. 

When using conduit wiring methods, which of the following colors of insulation or marking are permitted to identify "hot" phase conductors?
a.
black, red, and blue for 120/208-volt systems
b.
yellow, orange, and brown for 277/480-volt systems
c.
any colors except white, gray, or green
d.
all of these
 

 31. 

Wiring devices for use on nominal 120-volt circuits are marked ____.
a.
110 volts
b.
115 volts
c.
120 volts
d.
125 volts
 

 32. 

Alternating current, general-use snap switches are UL-listed to control motors rated up to ____ horsepower.
a.
1/2
b.
3/4
c.
2
d.
as marked on the switch
 

 33. 

NEC® 404.2(A) requires that switching be done only in the ____ conductor.
a.
ungrounded
b.
designated
c.
black
d.
red
 

 34. 

When receptacles or switches have No. 6-32 screws secured to them with small pieces of cardboard, these pieces of cardboard must be ____ when the wiring device is installed in a metal outlet box.
a.
left in place
b.
removed
c.
replaced with metal lock washers
d.
none of these
 

 35. 

To avoid inductive heating in metallic raceways, NEC® 300.20 requires that ____.
a.
all circuit conductors be run in the same raceway
b.
the grounded (neutral) conductor be oversized
c.
the equipment grounding conductor be bonded to the raceway
d.
none of these
 

 36. 

Which of the following underground feeder installations to a remote building "meets Code"?
mc036-1.jpg
a.
A
b.
B
 

 37. 

NEC® 406.3(D)(3) permits existing two-wire, nongrounded-type receptacles to be replaced with a ____ where no equipment grounding conductor exists.
a.
GFCI receptacle…and marked “No Equipment Ground”.
b.
two-wire nongrounding-type receptacle.
c.
three-wire grounding-type receptacle if fed from an upstream GFCI…and marked “GFCI Protected” and “No Equipment Ground.”
d.
all of these.
 

 38. 

Fixture whips used with fixtures in suspended ceilings are permitted to be of various types of cables or conductors in flexible raceways.  Regardless of the wiring method used, fixture whips are permitted to be a maximum of ____ long between outlet box and fixture.
a.
3 feet (900 mm)
b.
4 1/2 feet (1.4 m)
c.
6 feet (1.8 m)
d.
6 feet 7 inches (2 m)
 

 39. 

Leaving lamps on for long periods of time ____ lamp life.
a.
shortens
b.
extends
 

 40. 

Residential wiring plans generally show lighting and receptacle outlet locations but not circuits. The electrician should design the installation with which of the following in mind: ____.
a.
economy - minimizing the number and length of circuits
b.
convenience for the homeowner or other user
c.
National Electrical Code® requirements
d.
all of these
 

 41. 

Which of the following switch types is rarely used in residential wiring?
a.
single-pole
b.
double-pole
c.
three-way
d.
four-way
 

 42. 

A rotary light dimmer ____ suitable for use as a ceiling-suspended (paddle)fan speed control.
a.
is
b.
is not
 

 43. 

Ceiling-suspended (paddle) fans must be specially supported for all of the following reasons, except for ____.
a.
weight
b.
torque (twisting motion, particularly when first starting)
c.
safe grounding
d.
vibration
 

 44. 

Ceiling-suspended (paddle) fans weighing more than ____ pounds are required to be supported independently of the outlet box.
a.
15
b.
25
c.
35
d.
50
 

 45. 

Ceiling-suspended (paddle) fan speed can be controlled by ____.
a.
pull chain on the fan
b.
speed control mounted in a wall box
c.
remote-control similar to TV/VCR type
d.
any of these
 

 46. 

NEC® 210.12 requires that ____ protection be provided for all electrical outlets in residential bedrooms.
a.
ground-fault circuit interrupter (GFCI)
b.
arc-fault circuit interrupter (AFCI)
c.
both a and b
 

 47. 

Branch circuits are rated according to their ____.
a.
overcurrent protective device rating
b.
conductor size
c.
length
d.
impedance
 

 48. 

Cord-connected luminaires (fixtures), hanging luminaires (fixtures), track lighting, or ceilings-suspended (paddle) fans ____ permitted to be installed within the "tub zone" extending 3 feet (900 mm) horizontally and 8 feet (2.5 m) vertically from the top of the tub rim.
a.
are
b.
are not
 

 49. 

Which of he following kitchen equipment is permitted to be connected to the two 20-ampere small-appliance circuits required for the kitchen and dining room area?
a.
lighting
b.
fan
c.
clock outlet
d.
none of these
 

 50. 

Split-wiring of receptacles in kitchens and other locations where high-load appliances are used is not always practical when ____.
a.
decorator-type receptacles are used
b.
GFCI receptacles are used
c.
Type NM cable is used
d.
plastic boxes are used
 

 51. 

Duplex receptacles connected to a 20-ampere, small-appliance branch circuit in kitchens and dining rooms ____.
a.
may be rated 15 amperes
b.
may be rated 15- or 20-amperes
c.
may be rated 20 amperes
d.
all of the above
 

 52. 

The load for each small-appliance, branch circuit load is required to be calculated at ____.
a.
1,440 watts
b.
1,500 volt-amperes
c.
1,920 watts
d.
2,400 volt-amperes
 

 53. 

The 125-volt, 20-ampere receptacles installed to serve kitchen countertops are required to have GFCI protection ____.
a.
when they are within 6 feet (1.8 m)of the sink
b.
under all circumstances
c.
unless provided with assured grounding conductor protection
d.
none of these
 

 54. 

An electric circuit consists of the ____.
a.
power source
b.
conductors
c.
load
d.
all of the above
 

 55. 

Track lighting is not permitted to be installed less than ____ above the floor unless it has an open-circuit voltage of less that 30 volts RMS.
a.
5 feet (1.5 m)
b.
6 feet (1.8 m)
c.
6 feet 7 inches (2.0 m)
d.
7.5 feet (2.3 m)
 

 56. 

Which of the following is required in order to dim fluorescent fixtures?
a.
fluorescent dimmer
b.
dimming ballasts
c.
oversized neutral in the branch-circuit
d.
both a and b
 

 57. 

When laying out the wall receptacle locations in a bedroom, make sure that a receptacle is installed so that no point along the floor line is more than ____ from a receptacle.
a.
6 feet (1.8m)
b.
9 feet (2.7m)
c.
12 feet (3.7m)
 

 58. 

When an existing dryer or electric range is replaced, NEC® 250.140 ____ the grounded conductor of an existing individual branch circuit to be used for grounding the appliance frame.
a.
permits
b.
does not permit
 

 59. 

Cord sets rated 40, 45, or 50 amperes are usually called ____ cords, and cord sets rated 30 amperes are called ____ cords.
a.
SJT, SJ
b.
range, dryer
c.
heavy-duty, extra heavy-duty
d.
washer, dryer
 

 60. 

Household cooking device demand factors shown in Table 220.19 are normally ____ than the appliance nameplate rating.
a.
Less
b.
the same
c.
Higher
 

 61. 

A porcelain lampholder with a pull-chain ____ permitted to serve as the lighting outlet required by NEC® 210.70(A)(3).
a.
is
b.
is not
 

 62. 

To provide shock protection, low-voltage wiring systems are required by Article 411 to be ____.
a.
double-insulated
b.
grounded
c.
supplied though isolating transformers
d.
all of these
 

 63. 

When a single receptacle of any rating is installed on an individual branch circuit, the receptacle rating must not be ____ than the rating of the branch circuit.
a.
more
b.
less
 

 64. 

In unfinished basements, Type NM cable with conductors smaller than two 6 AWG or three 8 AWG installed perpendicular to joists is required to be run ____.
a.
through holes bored in the joists
b.
on running boards
c.
behind nailing strips
d.
both a and b
 

 65. 

Metallic raceways and metallic cable installations ____ generally considered to be adequate equipment grounding conductors.
a.
are
b.
are not
 

 66. 

Switch and outlet boxes are available with all the following size knockouts, except for ____.
a.
Trade size 3/8
b.
Trade size 1/2
c.
Trade size 3/4
d.
Trade size 1
 

 67. 

A short length of EMT is run between two panels. The ampacity values for the conductors in this EMT need not be derated as long as the length of the EMT does not exceed ____.
a.
12 in., 300
b.
18 in., 450
c.
24 in., 600
 

 68. 

Motor-circuit conductors are sized at 125% of the motor’s nameplate ampere rating, in conformance to ____.
a.
Table 310-16
b.
Table 310-19
c.
NEC® 430-6(A)(1) and 430.22.
d.
Chapter 9, Table 8
 

 69. 

NEC® 430.6(A)(1) requires that the motor full-load amperes listed in Tables 430.147 through 430.150 be used to size all of the following, except for ____.
a.
circuit conductors
b.
overload protectors
c.
ground-fault protection
d.
fuse size
 

 70. 

NEC® 110.14(C) states that for circuits rated 100 amperes and less, or for conductor sizes 14 AWG through 1 AWG, conductor ampacity shall be selected from the ____ column of Tables 310.16 through 310.19.
a.
60°C
b.
75°C
c.
90°C
d.
depends on derating factors
 

 71. 

In general, motor-overload protection is required not to exceed ____ percent of a motor's full-load current.
a.
125
b.
150
c.
225
d.
600
 

 72. 

NEC® ____ covers selection of time-delay fuses for motor branch-circuit short-circuit and ground-fault protection.
a.
NEC® 430.32(A)(1) and NEC® 430.52(C)(1)
b.
Table 430.52 and NEC® 430.32(A)(1)
c.
Table 430.52 and NEC® 430.52(C)(1)
d.
all of these
 

 73. 

When direct-burial Type UF or USE cables are installed beneath sidewalks or other paved areas in residential occupancies, they are required to be ____.
a.
installed in raceways
b.
connected to pole lighting standard grounding lugs
c.
installed a minimum of 18 in. (450 mm) deep
d.
both a and c
 

 74. 

"Submersible pump cable" supplied with well pump assemblies ____ suitable for directly burial when marked Type USE or Type UF.
a.
is
b.
is not
 

 75. 

Since the grounded (neutral) conductor is not permitted to be used for grounding the frames of electric ranges, ovens, or cooktops in new installations, these appliances require ____ power cords.
a.
three-wire
b.
double-insulated
c.
four-wire
d.
Listed
 

 76. 

The grounded conductor of a branch circuit is permitted to serve as the equipment grounding conductor for a replacement range or cooktop when all the following conditions are met, except for ____.
a.
the grounded conductor is not smaller than 10 AWG copper or 8 AWG aluminum
b.
the individual branch circuit is existing
c.
the grounded conductor is insulated, unless it is part of Type SE cable
d.
the branch circuit uses listed wire connectors
 

 77. 

Cord sets rated 30 amperes are usually called ____, and cord sets rated 40, 45, or 50 amperes are called ____.
a.
SJT, SJ
b.
dryer, range
c.
heavy-duty, extra heavy-duty
d.
washer, dryer
 

 78. 

NEC® 422.60(A) requires that an appliance nameplate show ____.
a.
the appliance rating in volts and amperes
b.
the appliance connected load in volts and watts
c.
the appliance branch circuit conductor size
d.
either a or b
 

 79. 

When an appliance is not marked with its maximum overcurrent protection, the branch circuit protection device is sized according to ____.
a.
Table 220-19
b.
the ampacity of the branch circuit conductors supplying the appliance
c.
30 amperes maximum
d.
none of these
 

 80. 

A "unit switch" used as a disconnecting means for an appliance shall ____.
a.
be horsepower-rated
b.
interrupt all ungrounded circuit conductors
c.
have a NEMA 3R enclosure when installed outdoors
d.
both a and b
 

 81. 

On all types and ratings of receptacles, the grounding blade is ____ than the others to insure that it makes its connection before the grounded conductors do and breaks its connection after they do (first make-last break).
a.
larger
b.
more durable
c.
longer
d.
tarnish-resistant
 

 82. 

Food-waste disposers include a small manual reset button to restart the motor if it overheats and goes off-line due to prolonged use, or something falling into the unit and jamming it.  This manual reset provides the ____ protection required by Code for this type of appliance.
a.
short-circuit
b.
ground-fault
c.
overload
d.
all of these
 

 83. 

The two 20-ampere small-appliance branch circuits required for the kitchen and dining room area are intended to supply ____ appliances.
a.
under 1/3 horsepower
b.
portable
c.
fixed-in-place
d.
all
 

 84. 

Thermostats and humidistats used in residential occupancies come in ____ models.
a.
line-voltage
b.
low-voltage
c.
solid-state
d.
all of these
 

 85. 

When a central air-conditioning unit label states "Maximum size time-delay fuse 50 amperes," what type of circuit-breaker is permitted to provide running overload protection?
a.
50-ampere circuit-breaker
b.
50-ampere HACR circuit-breaker
c.
65-ampere circuit-breaker
d.
circuit-breakers are not permitted for this application
 

 86. 

On circuits supplying cord-and-plug connected air conditioners, the branch circuit overcurrent protective device rating is not permitted to exceed ____.
a.
the ampacity of the branch circuit conductors
b.
the rating of the receptacle to which the air conditioner is connected
c.
50 percent of the total load of the air conditioner plus other loads on the same circuit
d.
either a or b, whichever is greater
 

 87. 

Residential thermostats should be located where they will not be influenced by ____.
a.
drafts or currents from air registers
b.
radiated heat from appliances, lamps, etc.
c.
direct rays of the sun
d.
all of these
 

 88. 

Motor-control circuit conductors must have overcurrent protection in accordance with ____.
a.
NEC® 240-1
b.
NEC® 430-72
c.
NEC® 440-18(d)
d.
Article 725
 

 89. 

Internal control circuitry of motorized equipment, such as heating, ventilating, and air-conditioning, is generally covered by ____.
a.
Article 430
b.
Article 440
c.
listing agency standards such as Underwriters’ Laboratories
d.
none of these
 

 90. 

External control circuitry of motorized equipment such as heating, ventilating, and air-conditioning is generally covered by ____.
a.
Article 430
b.
Article 440
c.
Article 725
d.
both a and c
 

 91. 

Because they have internal overload protection, listed Class 2 and Class 3 transformers are permitted to be supplied by branch circuits having overcurrent protection not exceeding ____ amperes.
a.
15
b.
20
c.
30
d.
50
 

 92. 

Class 2 and Class 3 power source voltage limitations, current limitations, and overcurrent protection requirements are found in ____.
a.
Article 220
b.
Article 240
c.
Article 725
d.
Chapter 9, Tables 11(A), 11(B)
 

 93. 

It ____ permitted to install Class 2 wiring in the same raceway or enclosure as electric light and power wiring.
a.
is
b.
is not
 

 94. 

Signaling circuit is defined in ____.
a.
Article 100
b.
NEC® 725.1
c.
NEC® 725.10(C)
d.
NEC® 800.3(B)(2)
 

 95. 

Which of the following types of conduit is (are) permitted to be used for service masts?
a.
rigid nonmetallic conduit
b.
intermediate metal conduit
c.
rigid metal conduit
d.
both b and c
 

 96. 

A mast service is installed on a residence. The minimum clearance above the roof for the service conductors is ____ provided the conductors pass over not more than 4 ft (1.2 m) of the overhanging portion of the roof.
a.
18 in. (450 mm)
b.
24 in. (600 mm)
c.
36 in. 900 mm)
 

 97. 

GFCI protection for personnel ____ protect a person against the sensation of feeling a shock.
a.
does
b.
does not
 

 98. 

So-called "structured premises wiring systems" are defined in standards published by ____.
a.
National Electrical Manufacturer's Association (NEMA)
b.
Underwriters Laboratories Inc. (UL)
c.
Institute of Electrical and Electronics Engineers (IEEE)
d.
Electronic Industries Association/Telecommunications Industry Association (EIA/TIA)
 

 99. 

You are installing individual cables from a central distribution panel to all locations in your home where you plan on using computers, TV, cable modems, and similar electronic equipment. In addition to installing 125-volt receptacles, which of the following cables should be installed.
a.
Two 2-conductor bell wire cables
b.
At least one RG-6 (75-ohm) coaxial cable
c.
At least one four-pair Category 5 or 5e cable
d.
Two 2-conductor thermostat wire that has an outer jacket
e.
Both b and c
 

 100. 

The conductors between a standby generator and the panel that serves the critical loads shall be sized at not less than ____ percent of the generators nameplate current rating.
a.
115
b.
175
c.
225
 



 
Check Your Work     Start Over